Model | HTS-150A | ||
Nominal cooling capacity | 7ºC | kcal/h | 350192 |
kw | 407.2 | ||
12ºC | kcal/h | 421830 | |
kw | 490.5 | ||
Input power | kw | 133 | |
Power source | 3PH 380V~415V 50HZ/60HZ | ||
Refrigerant | |||
Type | R22 | ||
Charge | kg | 105 | |
Control | Thermostatic expansion valve | ||
Compressor | |||
Type | Semi-Hermetic screw | ||
Power | KW | 122.2 | |
Start mode | Y-△ | ||
Capacity control | % | 0-25-50-75-100 | |
Evaporator | |||
Type | Shell and tube(ss plate heat exchanger) | ||
Chilled water volume | m3/h | 69.5 | |
Tank volume | Iiter | 41 | |
Pipe connection | Inch | 5 | |
Condenser | |||
Type | air cooled type high efficiency finned copper tube | ||
Fan | |||
Type | Big volume & low noise axial fan | ||
Power | kw | 0.9*12 | |
Air volume | m³/h | 181440 | |
Safety devices | Compressor inner protection, over current protection, high/low pressure protection, over temperature protection, flow rate protection, phase sequence/phase missing protection, low level coolant protection, anti freezing protection, exhaust overheat protection | ||
Dimension | |||
Length | mm | 5980 | |
Width | mm | 2000 | |
Height | mm | 2170 | |
Net weight | kg | 3200 | |
Running weight | kg | 3500 | |
The above specifications are according to the following design conditions: 1. Chilled water inlet/outlet temperature 12ºC/7ºC. 2. Cooling air inlet/outlet temperature 35ºC/43ºC. Cooling capacity of R407C unit will be 5% lower than R22 unit We reserve the right to modify the specifications without further notice. |
Model | HTS-150AD | ||
Nominal cooling capacity | 7ºC | kcal/h | 339528 |
kw | 394.8 | ||
12ºC | kcal/h | 409016 | |
kw | 475.6 | ||
Input power | kw | 137.6 | |
Power source | 3PH 380V~415V 50HZ/60HZ | ||
Refrigerant | |||
Type | R22 | ||
Charge | kg | 52*2 | |
Control | Thermostatic expansion valve | ||
Compressor | |||
Type | Semi-Hermetic screw | ||
Power | KW | 63.4*2 | |
Start mode | Y-△ | ||
Capacity control | % | 0-25-50-75-100 | |
Evaporator | |||
Type | Shell and tube(ss plate heat exchanger) | ||
Chilled water volume | m3/h | 68 | |
Tank volume | Iiter | 41 | |
Pipe connection | Inch | 5 | |
Condenser | |||
Type | air cooled type high efficiency finned copper tube | ||
Fan | |||
Type | Big volume & low noise axial fan | ||
Power | kw | 0.8*12 | |
Air volume | m³/h | 149040 | |
Safety devices | Compressor inner protection, over current protection, high/low pressure protection, over temperature protection, flow rate protection, phase sequence/phase missing protection, low level coolant protection, anti freezing protection, exhaust overheat protection | ||
Dimension | |||
Length | mm | 5980 | |
Width | mm | 2000 | |
Height | mm | 2170 | |
Net weight | kg | 4100 | |
Running weight | kg | 4500 | |
The above specifications are according to the following design conditions: 1. Chilled water inlet/outlet temperature 12ºC/7ºC. 2. Cooling air inlet/outlet temperature 35ºC/43ºC. Cooling capacity of R407C unit will be 5% lower than R22 unit We reserve the right to modify the specifications without further notice. |
Brand strength | We are the professional and top supplier of industrial chiller with 20 years experience. |
Professional Guidance | Professional and experienced technician & sales team service to the oversea market, offering professional solution according to requirements; |
Fast delivery | 1/2hp to 50hp air-cooled chillers in stock for immediately delivery; |
Golden service | Service call response within 1 hour, solution offered within 4hrs, and own oversea installation and maintenance team |