Model | HTS-75W | ||
Nominal cooling capacity | 7ºC | kcal/h | 205540 |
kw | 239.0 | ||
ton | 68 | ||
12ºC | kcal/h | 245444 | |
kw | 285.4 | ||
ton | 81 | ||
Input power | kw | 50.3 | |
Power source | 3PH 380V~415V 50HZ/60HZ | ||
Refrigerant | |||
Type | R22 | ||
Charge | kg | 42 | |
Control | Thermostatic expansion valve | ||
Compressor | |||
Type | Semi-Hermetic screw | ||
Power | KW | 50.3 | |
Start mode | Y-△ | ||
Capacity control | % | 0-25-50-75-100 | |
Evaporator | |||
Type | Shell and tube(ss plate heat exchanger) | ||
Chilled water volume | m3/h | 39.5 | |
Tank volume | Iiter | 42 | |
Pipe connection | Inch | 3 | |
Condenser | |||
Type | Shell and tube | ||
Cooling water flow | m³/h | 49.2 | |
Water pressure drop | kPa | 43 | |
Pipe connection | inch | 3 | |
Safety devices | Compressor inner protection, over current protection, high/low pressure protection, over temperature protection, flow rate protection, phase sequence/phase missing protection, low level coolant protection, anti freezing protection, exhaust overheat protection | ||
Dimension | |||
Length | mm | 2800 | |
Width | mm | 950 | |
Height | mm | 1800 | |
Net weight | kg | 1800 | |
Running weight | kg | 1980 | |
The above specifications are according to the following design conditions: 1. Chilled water inlet/outlet temperature 7ºC/12ºC. 2. Cooling air inlet/outlet temperature 30ºC/38ºC. Cooling capacity of R407C unit will be 5% lower than R22 unit We reserve the right to modify the specifications without further notice. |